Review a weekly run breakdown for fire pump maintenance below. Contact Complete Fire Pump Service with any questions to have or to ensure your fire protection needs are taken care of.

CP_NEW_logoWHT_BLK_left.png

Fire Pump Maintenance - Weekly Run

  • Call alarm service and inform them that system is being tested.

  • Announce to occupants of the building to disregard fire alarms for the next hour.

  • Open main drain slightly to drop pressure and watch jockey pump turn on. 

  • Close valve and watch jockey pump build pressure and shut off. 

  • Open main drain again and drop pressure until jockey pump turns on.

  • Open main drain a little more so pressure drops faster than jockey pump can maintain.

  • Watch fire pump turns on.

  • Close main drain valve.

  • Check that casing relief valve is running a full stream of water.

  • Check that packing is dripping.

  • Grease pump bearings with one pump of the grease gun handle.

  • Observe that the pump discharge gauge is reading much higher than the suction gauge.

  • Push stop button on controller and observe that fire pump shuts down.

  • Call alarm service to inform them the test is finished.

Note: Create a log of your weekly fire pump runs. Here you can download the sample of the log form.